How to tell if a door is fire rated
Most fire doors look like any other door. The rating tells you how long the door held back fire in a test, and the label tells you where that rating came from. Neither one says whether the door still works today, which is what a regular check is for.
What FD30, FD60 and the S mean
An FD rating comes from the British fire test for doors, BS 476-22. The number is the minutes the door kept its integrity in the test, so an FD30 door held back fire for 30 minutes and an FD60 door for 60. An S on the end, as in FD30S, means the door also limits smoke getting through at room temperature.
Newer doors are often rated to the European test instead, written as E30 or E30 Sa. The building guidance for England lists both side by side for now. From 2 September 2029 it will use only the European ratings, so new doors will increasingly be labelled that way.
The rating belongs to the whole door as it was tested, including its frame, seals, glazing and hardware. The building guidance warns that small differences in detail can significantly affect the rating, which is why a new letterbox or glass panel needs to suit that door.
Which doors need which rating
For new blocks of flats in England, the building guidance sets FD30S as the minimum for a flat front door that opens onto a shared corridor or landing, and for the doors into a protected stairway. A door in a wall that separates two buildings needs at least 60 minutes. In an existing building, your fire risk assessment is what decides whether each door is good enough for where it is.
Finding the label
A fire door from a third party scheme carries a label on the top edge of the door, in the frame, or as a plug set into the door. The label has a unique code that traces the door back to its certificate and maker. Government guidance says modern fire doors should show a visible fire resistance rating.
Some buildings also put an inspection tag on each fire door. A tag records when the door was last inspected and by whom. It is not the rating, so look for the maker’s label as well.
No label does not mean the door has failed. Government guidance for England says a door without a certificate, or without strips and seals, is not unfit for that reason alone. A door that met the standard when the block was built, or when the door was made, will usually still protect the escape route, as long as it is undamaged and the gaps round it are not too large. Whether it is good enough is a question for the fire risk assessment, not for a self check.
Does a flat front door need a rating?
In a new block, yes: FD30S with a self closer. In an existing block, the door needs to be good enough for the risk, and your fire risk assessment says whether it is. Government guidance is clear that the 2022 England regulations are not there to make leaseholders replace older doors that met the standard of their day.
If a resident swaps their front door, the guidance says the new one must be fire resisting and fitted by a competent person, and the resident must give its technical details to whoever is responsible for the building. The change should be agreed with them first.
Checking a door’s rating
- Look for a label or plug on the top edge of the door and in the frame. You may need a step to see the top edge
- Photograph the label and write down any code on it, so the maker can trace the certificate
- Compare the door with the others in the building. One flat door of a different design may mean it has been replaced
- Look for changes since it was fitted, such as a new letterbox or a hole where a lock was taken out
- Check the door has a self closer and shuts fully from wide open and from around 15 degrees. Our guide to fire door closers has the full check
- If there is no label, record that and check what your fire risk assessment says about the door, rather than marking it as a fail
What people ask about ratings
What does FD30 mean?
The door held back fire for 30 minutes in the British fire test for doors, BS 476-22. FD60 means 60 minutes in the same test.
What does the S mean in FD30S?
The door also limits smoke leakage at room temperature, so it is tested against smoke as well as fire.
How can I tell if a door is fire rated without a label?
Ask the maker or supplier, if you know who they are. Otherwise it is a question for your fire risk assessment or a fire door inspection by a competent person. A missing label on an older door does not on its own mean the door is unfit.
Does a fire rating last for ever?
The rating describes the door as it was tested. Wear and tear or later changes to the door can undermine it, which is why fire doors need to be kept in good repair and checked regularly.
A plain summary, not legal advice
This guide follows the rules in England. Wales shares the Fire Safety Order but not the 2022 England regulations, and Scotland and Northern Ireland have their own fire safety law. Your fire risk assessment is the place that says what applies to your building, and a self check never replaces a fire door inspection by a competent person.
We put fire doors right across County Durham, Teesside and Tyne and Wear. If you are further away, a dated report from Door by Door is exactly what a local fire door specialist will want to see.
Tell us where to start
Ring Wayne Cator, our Managing Director, or send us the details and we will come back to you.